The SSB SBL 200-12i is a sealed, maintenance-free lead-acid battery manufactured using VRLA-AGM technology. The electrolyte is absorbed in a glass mat separator, eliminating the need to top up water during operation. The model is designed for both standby and cyclic operation.
The battery belongs to the SBL series, intended for applications requiring a stable backup power supply. Its designed service life in standby operation is up to 12 years. With a capacity of 200 Ah and a nominal voltage of 12 V, it is suitable for UPS systems, telecommunications power plants and central emergency power supply systems.
VRLA-AGM technology – sealed, maintenance-free design
Nominal voltage: 12 V
Nominal capacity: 200 Ah
Suitable for standby and cyclic operation
Designed service life of up to 12 years in standby operation
No need to top up water
M8 female-thread terminals
Suitable for large backup power installations
Manufacturer: SSB Battery
Series: SBL
Model: SBL 200-12i
Part number: SBL 200-12i
EAN code: 5902311970810
Technology: VRLA-AGM
Type: sealed, maintenance-free lead-acid battery
Nominal voltage: 12 V
Nominal capacity: 200 Ah
Internal resistance: approx. 4 mΩ
Self-discharge: approx. 3% of capacity per month at 25°C
Terminals: M8 female thread
Weight: approx. 66 kg
Length: 522 mm
Width: 240 mm
Case height: 218 mm
Overall height: 240 mm
Designed service life in standby operation: up to 12 years
Warranty: 24 months
Float charging voltage: 13.6–13.8 V
Cyclic charging voltage: 14.5–14.9 V
The charging voltage should be adjusted to the operating mode and the manufacturer's recommendations to ensure proper battery operation.
UPS emergency power supply systems
Central battery systems and backup power supplies
Telecommunications power plants
Alarm and access control systems
Communication equipment
Medical devices
Emergency lighting
Cash registers and other devices requiring battery power
Due to its weight and dimensions, check the available space, mounting method and compatibility of the battery parameters with the requirements of the device or power supply system before installation.
We have made every effort to ensure that the above data is correct, but we do not guarantee that the published information does not contain errors, which, however, cannot constitute the basis for any claims.